2.3 Personal Safety
Safety Zone
Ensure any personnel entering a safety zone within a four foot area around any operating
inverter wear appropriate Personal Protective Equipment (PPE) as mandated by national,
state and local authorities.
Medical and First Aid Treatment
Personnel working in and around operating power generation equipment should be
trained in Arc Flash Hazard, Fire Extinguisher selection and use, First Aid, Cardio
Pulmonary Resuscitation (CPR) and Automated External Debrillator (AED) use (if
available).
Safety Equipment
Minimum Requirements
Authorized service personnel performing operations on this unit should have the
following available:
• Consult NFPA 70E, or applicaple local standards, for PPE requirements on switch
gear operating at less than 600V
• Electrical Hazard Footwear (ANSI Z41/Z85 rated)
• Lock Out Tag Out (LOTO) Kit
• Appropriate meter to verify the circuits are safely de-energized (1000VAC and DC
rated, minimum)
• Any other equipment as applicable to your operation as required by national, state
and local regulations
2.4 Wiring Requirement
!
WARNING
In accordance with the NEC and ANSI/NFPA70 or applicable Canadian
Electrical Code, connect only to a circuit with a properly rated maximum
branch circuit overcurrent protection. Recommended ratings are:
Model 480VAC 600VAC
PVP250kW 400A 350A
PVP260kW 400A N/A
PVP260kW-LV 400A N/A