PV Powered 2500 Guía de instalación Pagina 47

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 66
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 46
SMA Technologie AG Technical Data
Installation Guide SB25_30-11:SE0307 Page 47
8.4.3 Country-specific Parameter Settings
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 8.4.2 "Parameter Settings for Germany" (Page 45).
Sunny Boy SB 2500
Sunny Boy SB 3000
Name Short
descr.
Country settings
Germany Great Britain Spain
Default GER/VDE0126-1-1 GB/G83 SP/RD1663
dFac-Max Hz/s 4 0.2 2
dZac-Max mOhm 700 350 350
Fac-delta- Hz 2.45 0.5 0.98
Fac-delta+ Hz 0.19 0.5 0.98
I-NiTest mA 8000 0 0
T-Start s 10 180 10
Uac-Min V 198 209 199
Uac-Max V 260 261 250
Name Short
descr.
Country settings
Germany Great Britain Spain
Default GER/VDE0126-1-1 GB/G83 SP/RD1663
dFac-Max Hz/s 0.25 0.2 2
dZac-Max mOhm 700 350 350
Fac-delta- Hz 2.45 0.5 0.98
Fac-delta+ Hz 0.19 0.5 0.98
I-NiTest mA 9000 0 0
T-Start s 10 180 10
Uac-Min V 198 209 199
Uac-Max V 260 261 250