SMA Technologie AG Technical Data
Installation Guide SB25_30-11:SE0307 Page 45
8.4.2 Parameter Settings for Germany
The grayed-out parameters are only displayed in installer mode.
Warning!
Unauthorized changes to the operating parameters may result in:
• injury or accidents as a result of changing the internal safety routines
in the Sunny Boy,
• voiding the Sunny Boy's operating approval certificate,
• voiding the Sunny Boy's warranty.
Never change the parameters of your Sunny Boy without express
authorization and instructions.
Name Short
descr.
Value range Factory setting
Sunny Boy
SB 2500
Sunny Boy
SB 3000
ACVtgRPro V 230 ... 300 253 253
AntiIsland-
Ampl*
grd 0 ... 10 0 0
AntiIsland-Freq* mHz 0 ... 2000 500 500
Betriebsart MPP,
Konstantspg.,
Stop, Turbine
MPP MPP
Default * GER/VDE0126-
1-1, GB/G83,
Off_Grid,
SP/RD1663,
Other, trimmed
GER/VDE0126-1-1 GER/VDE0126-1-1
dFac-MAX * Hz/s 0.005 ... 4.0 4 4
dZac* mOhm 0 ... 20000 700 700
E_Total kWh 0 ... 200000
Fac-delta+ * Hz 0 ... 4.5 0.19 0.19
Fac-delta- * Hz 0 ... 4.5 2.45 2.45
h_Total h 0 ... 200000
I-NiTest * mA 0 ... 15000 8000 9000
Speicher/
Storage
permanent,
volatil
permanent permanent