Installation Requirements SMA Technologie AG
Page 16 SB25_30-11:SE0307 Installation Guide
Rating for a Line Circuit Breaker in a Photovoltaic Power Generating
System Operated in Parallel to the Low Voltage Grid
Various factors should be taken into account when selecting line circuit breakers. These
include, for example:
The type of cable used (conductor material and insulation)
Ambient temperatures affecting the cables (higher temperatures result in a reduced
maximum current load)
Method of routing the cable (reduces the maximum current load)
Bundling cables together (reduces the maximum current load)
Loop impedance [Z] (in the event of a body contact this limits the current that can
flow and therefore determines the response behavior of the circuit breaker)
Sufficient distance between the circuit breakers so as to avoid undue heating (heat
can trigger the circuit breaker early)
•Selectivity
Protection class of the connected load (VDE 0100, part 410), Protection against
electric shock
The following standards should be followed in all cases:
Please pay attention to section 10 "Rating for a Line Circuit Breaker" (Page 55).
DIN VDE 0298-4 (Cable routing and current-carrying capacity)
DIN VDE 0100, part 430 (Protective measures; protection of cable and
cords against overcurrent)
DIN VDE 0100, part 410 (Protective measures; protection against electric
shock)