SMA Solar Technology AG Technical Data
Installation Guide SB25_30-IEN092520 43
General data SB 2500 SB 3000
EC Declaration of Conformity You can download the EC Declaration of
Conformity in the download area at
www.SMA.de/en under Certificates.
Protection rating per DIN EN 60529 IP65
Dimensions (W x H x D) approx. 434 mm x 295 mm x 214 mm
Weight approx. 30 kg approx. 32 kg
Climatic conditions according to DIN EN 50178:1998-04
Location of type C: Class 4K4H
extended temperature range:
-25 °C ... +60 °C
extended humidity range:
0 ... 100 %
extended air pressure range:
70 kPa ... 106 kPa
Transport of type E: Class 2K3
Temperature range -25 °C ... +70 °C
Operating temperature range -25 °C ... +60°C
Max. operating altitude 2000 m above mean sea level
Topology LF transformer
Protection class I
Noise emission (typical) 33 dB(A) 30 dB(A)
Protective function DC side
All-pole disconnection unit on the DC input side Electronic Solar Switch (ESS)
DC plug connector
Overvoltage protection Thermally monitored varistors
Personal protection Insulation monitoring (Riso > 1MOhm)
Reverse polarity protection via short-circuit diode
Protective function AC side
Short-circuit proof Current control
All-pole disconnection unit on grid side Automatic disconnection device
(SMA Grid Guard 2.1), double design
Communication interfaces
RS485 (galvanically isolated) optional
Radio optional