Grid-Tied Residential Inverters
Installation and Operation Manual
7
CAUTION
The National Electrical Code (NEC) requires that the inverter be connected to a
dedicated circuit with no other outlets or devices connected to the same circuit.
See NEC Section 690-64(b)(1). The NEC also places limitations on the size of the
inverter and the manner in which it is connected to the utility grid. See NEC Section
690-64(b)(2).
To reduce the risk of fire, connect the inverter to the appropriate size breaker (See
Table 3-1 for required branch circuit protection). Maximum branch-circuit over-
current protection calculated in accordance with the National Electrical Code (NEC),
ANSI/NFPA 70.
!
Figure 3-4 Inverter with Mounting Bracket in Place
NOTE: Leave the inverter cover off to allow for electrical connection
described in 3.2 Electrical Connections.
3.2 Electrical Connections