Figure 28: Conduit installation and wiring routing
Conduit ttings need to be water tight with either a NEMA 4, 4X, 6, or 6X rating.
Once conduit and ttings are installed, route wiring through the conduit and tting and allow a 6
inch strain relief service loop within the wiring box compartment.
0.5 inch
4.8.4 PV array string input connections
To ensure maximum protection against hazardous contact voltages
while assembling photovoltaic installations, both the positive and
the negative leads must be strictly isolated electrically from the
ground. All string fuses must be removed from the wiring box.
DANGER!
DANGER!
6 inches
Risk of electric shock and re. Use only with PV modules that
are listed for use with system voltage of 600V.
Electric shock hazard. The DC conductors of this photovoltaic
system are ungrounded and may be energized.
Electric shock hazard. The DC conductors of this photovoltaic
system are ungrounded but will become temporarily
grounded without indication when the inverter measures
the PV array isolation.
WARNING!
AVERTISSEMENT!
Verify all DC source circuit voltages and polarities with a volt
meter because damage to the inverter could result if incorrect
DC input voltages or polarity is connected to it. After verica-
tion of correct voltage and polarity, DC fuses can be installed.
CAUTION!
PRUDENCE!