9.2 Output AC Specifications
The PVI 3000S-5300 is designed to feed power into a standard 60Hz, 240 or 208V AC utility
service or 208V AC provided within a facility by a step down transformer (for example, from 480V
AC service). As required by NEC, there must be a dedicated 2-pole circuit breaker for the PV
inverter connection. This circuit breaker (and wiring) must have a rating of 20, 25 or 30A
depending on the model. The inverter is designed to work with the range of AC voltage for a
240VAC or 208V service defined by UL1741/IEEE1547.
PVI 3000S PVI 4000S PVI 5000S PVI 5300 Unit
Operating AC Voltage range (240V)
Operating AC Voltage range (208V)
Default over/under voltage trip points and
times
per IEEE Std 1547-2003, Table 1
perating frequency ( and frequency
range)
60 (59.3 – 60.5) Hz
Output Current Protection
Maximum Backfeed Current to PV
Total Harmonic distortion (THD, @ full
power)
< 3%
Anti-islanding protection
Part 15 B
Table 9.2.1 – AC Output Specifications
9.3 General Specifications
PVI 3000S PVI 4000S PVI 5000S PVI 5300 Unit
Convection and fan assist
to 6 AWG input and output
UL1741/IEEE1547, IEEE1547.1, CSA22.2#107.1,
ANSI62.41.2, FCC part 15 B
Table 9.3.1 – General Specifications